IEC 61511
Encyclopedia
IEC 61511 is a technical standard which sets out practices in the engineering of systems that ensure the safety of an industrial process through the use of instrumentation. Such systems are referred to as Safety Instrumented Systems. The title of the standard is "Functional safety - Safety instrumented systems for the process industry sector".

Scope

The process industry sector includes many types of manufacturing processes, such as refineries, petrochemical, chemical, pharmaceutical, pulp and paper, and power. The process sector standard does not cover nuclear power facilities or nuclear reactors. IEC 61511 covers the application of electrical, electronic and programmable electronic equipment. While IEC 61511 does apply to equipment using pneumatic or hydraulic systems to manipulate final elements, the standard does not cover the design and implementation of pneumatic or hydraulic logic solvers.

This standard defines the functional safety requirements established by IEC 61508
IEC 61508
IEC 61508 is an international standard of rules applied in industry. It is titled "Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related Systems"....

 in process industry sector terminology. IEC 61511 focuses attention on one type of instrumented safety system used within the process sector, the Safety Instrumented System
Safety instrumented system
A Safety Instrumented System is a form of process control usually implemented in industrial processes, such as those of a factory or an oil refinery. The SIS performs specified functions to achieve or maintain a safe state of the process when unacceptable or dangerous process conditions are detected...

 (SIS). The standard does not provide requirements for other instrumented safety systems, such as fire and gas systems, safety alarms, or safety controls.

History

In 1998 the IEC
International Electrotechnical Commission
The International Electrotechnical Commission is a non-profit, non-governmental international standards organization that prepares and publishes International Standards for all electrical, electronic and related technologies – collectively known as "electrotechnology"...

, which stands for International Electrotechnical Commission
International Electrotechnical Commission
The International Electrotechnical Commission is a non-profit, non-governmental international standards organization that prepares and publishes International Standards for all electrical, electronic and related technologies – collectively known as "electrotechnology"...

 published a document, IEC 61508
IEC 61508
IEC 61508 is an international standard of rules applied in industry. It is titled "Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related Systems"....

, entitled: “Functional safety of electrical/electronic/programmable electronic safety-related systems”. This document sets the standards for safety-related system design of hardware and software. IEC 61508 is generic functional safety standard, providing the framework and core requirements for sector specific standard. Three sector specific standards have been released using the IEC 61508 framework, IEC 61511 (process), IEC 61513 (nuclear) and IEC 62061 (manufacturing). IEC 61511 provides good engineering practices for the application of safety instrumented systems in the process sector.

In the United States ANSI/ISA 84.00.01-2004 was issued in September 2004. It primarily mirrors IEC 61511 in content with the exception that it contains a grandfathering clause:
For existing safety instrumented systems (SIS)
Safety instrumented system
A Safety Instrumented System is a form of process control usually implemented in industrial processes, such as those of a factory or an oil refinery. The SIS performs specified functions to achieve or maintain a safe state of the process when unacceptable or dangerous process conditions are detected...

 designed and constructed in accordance with codes, standards, or practices prior to the issuance of this standard (e.g. ANSI/ISA 84.01-1996), the owner/operator shall determine and document that the equipment is designed, maintained, inspected, tested, and operated in a safe manner.


The European standards body, CENELEC, has adopted the standard as EN 61511. This means that in each of the member states of the European Union, the standard is published as a national standard. For example, in Great Britain, it is published by the national standards body, BSI, as BS EN 61511. The content of these national publications is identical to that of IEC 61511. Note, however, that 61511 is not harmonized under any directive of the European Commission.

The Standard

IEC 61511 covers the design and management requirements for SISs from cradle to grave. Its scope includes: initial concept, design, implementation, operation, and maintenance through to decommissioning. It starts in the earliest phase of a project and continues through startup. It contains sections that cover modifications that come along later, along with maintenance activities and the eventual decommissioning activities.

The standard consists of three parts:
  1. Framework, definitions, system, hardware and software requirements
  2. Guidelines in the application of IEC 61511-1
  3. Guidance for the determination of the required safety integrity levels
    Safety Integrity Level
    Safety Integrity Level is defined as a relative level of risk-reduction provided by a safety function, or to specify a target level of risk reduction. In simple terms, SIL is a measurement of performance required for a Safety Instrumented Function ....



ISA 84.01/IEC 61511 requires a management system for identified SIS. An SIS is composed of a separate and independent combination of sensors, logic solvers, final elements, and support systems that are designed and managed to achieve a specified safety integrity level (SIL). An SIS may implement one or more safety instrumented functions (SIFs), which are designed and implemented to address a specific process hazard or hazardous event. The SIS management system should define how an owner/operator intends to assess, design, engineer, verify, install, commission, validate, operate, maintain, and continuously improve their SIS. The essential roles of the various personnel assigned responsibility for the SIS should be defined and procedures developed, as necessary, to support the consistent execution of their responsibilities.

ISA 84.01/IEC 61511 uses an order of magnitude metric, the SIL, to establish the necessary performance. A hazard and risk analysis is used to identify the required safety functions and risk reduction for specified hazardous events. Safety functions allocated to the SIS are safety instrumented functions; the allocated risk reduction is related to the SIL. The design and operating basis is developed to ensure that the SIS meets the required SIL. Field data are collected through operational and mechanical integrity program activities to assess actual SIS performance. When the required performance is not met, action should be taken to close the gap, ensuring safe and reliable operation.